Power wiring 695 6 size conductors that supply fire pump motors and accessory equipment for no less than 125 percent of the sum of the motor full load currents as listed in table 430 148 and or 430 150 plus 100 percent of the ampere rating of the fire pump accessory equipment.
Fire pump motor overcurrent protection sizing.
To size its conductor ampacity we calculate it as 1 25 times the fire pump fla 302a x 1 25 377a 400a ampacity.
See example 3 to size a transformer.
I did the wiring for a 75 horsepower 480 volt three phase fire pump motor with a nameplate full load current rating of 94 amperes.
Secondary overcurrent protection is not permitted 695 5 b.
You cannot provide secondary overcurrent protection.
To size its ocpd we size it based on the locked rotor current of the fire pump per nec 695 4 b 1.
So for a 250hp fire pump motor its ocpd rating would be 2000a.
If a transformer supplies an electric fire pump motor size it at least 125 of the sum of the fire pump and pressure maintenance pump s motor loads and 100 of the ampere rating of the fire pump s accessory equipment 695 5 a.
The overcurrent protection complies with the earlier requirements in that it is intended only for short circuit fault protection and is set.
The feeder conductors to the fire pump are 1 awg copper with thwn insulation in 1 25 inch rigid metal conduit and liquid tight flexible metal conduit.