Fire pump packing.
Most fire pumps will have six rings of packing.
Post navigation fire pump parts accessories availability hubbell launches a new line of metron fire pump controllers.
If it is a horizontal split case there will be six rings of packing on both sides of the shaft and in order to keep the shaft lubricated water needs to drip past the shaft to keep it lubricated.
Thoroughly clean and inspect the stuffing box.
Proper pump packing installation.
Coat each new packing ring with pak lube go jo or some type of liquid soap.
But as the pump and packing start to set in you can expect a couple years of consistent and reliable service.
Feel the packing gland be careful of the rotating shaft to see if the packing gland is too hot or uneven which will result in damage to the pump shaft.
Never use anti seize or any metallic based compound on the pump packing.
Hale zm packing kit.
Peerless fire pump installations ul listed ulc listed or fm approved deliver superior fire protection to facilities worldwide.
Adjust the followers one flat or of a turn every 30 minutes or until the leakage is controlled.
Products 6 sort by.
Centrifugal fire pump packing.
Stocking packing for your waterous hale darley c entrifugal fire pump.
Waterous fire pump packing cmu 1993 up wtrs.
Field tested products are designed for reliability and longevity and include a broad selection of pumps drives controls baseplates and accessories.
When people such as maintenance crews etc.
Packing adjustment will be more frequent at first.
Are inside the building they see the drip and think that.
Pentair aurora s commitment to fire suppression system performance and quality service goes beyond just 100 years of perfecting fire pump design.
Remove all of the used pump packing rings and the lantern ring.
We also offer kits from patterson and fair banks please contact us with your pump information for purchasing.
The packing gland should be placed on top of the packing.
Tighten down the followers.
Waterous mechanical seal kit.
Replace worn shaft sleeve if needed.
Gain system design advantages by leveraging our expertise in evolving standards and local fire codes.
Peerless fireconnect allows you to access complete fire pump system information 24 7 anytime and anywhere via your smartphone tablet laptop or desktop.
Posted in fire pumps general information and tagged extend pump service life packing gland adjustments on april 8 2016 by admin.
Repacking and regular maintenance is import for protecting your building as well as preventing expensive repairs later.